RGB32Ha

RGB32H miniature circuit breaker (hereafter simply referred to as breakers), the rated insulation voltage of the breakers is 300V. In the circuit of AC50Hz/60Hz, rated working voltage 230V or below ,rated current from 15A to 32A, the breakers take the role of infrequent turn-on or turn-off .The breakers has overload protection devices ,so as to protect the circuit and the power equipment against damage.
服务热线+86-137-7773-8060 +86-577-89051920

GENERAL

RGB32H miniature circuit breaker (hereafter simply referred to as breakers), the rated insulation voltage of the breakers is 300V. In the circuit of AC50Hz/60Hz, rated working voltage 230V or below ,rated current from 15A to 32A, the breakers take the role of infrequent turn-on or turn-off .The breakers has overload protection devices ,so as to protect the circuit and the power equipment against damage.

The breakers could be installed vertically or horizontally.

The breakers comply with the demands of the following standards:

EN/IEC60947-1: Low-voltage switchgear and controlgear——Part1:General rules.

EN/IEC60947-2: Low-voltage switchgear and controlgear——Part 2:Circuit-breaker.

NORMAL SERVICE AND MOUNTING CONDTIONS

The ambient air temperature does not exceed +40℃ and its average over a period of 24h does not exceed +35℃,the lower limit of the ambient air temperature is -5℃.

The altitude of the site of installation does not exceed 2000m.

The relative humidity of the air does not exceed 50% at a maximum temperature of +40℃ , higher relative humidities may be permitted at lower temperature,e.g.90% at +20℃. Special measures may be necessary in cases of occasional condensation due to variations in temperature.

Pollution degree 2.

Installing category: III

There must be not any explosive medium, and there must be not any gas which would corrode metal or any conducting dust which would destory the insulation

The place would not be invaded by rain and snow. 


MAIN TECHNICAL PERFORMANCE INDEX

    Frame

30

    Type

RGB32Ha

RGB32Hb

    Pole number

2

2

    Rated current(A)                 In

15(16),20,30(32)

15(16),20,30(32)

    Rated insulation voltage(VAC)    Ui

300

300

    Rated impulse withstand vol(V)   Uimp

4000

4000

    Rated operational voltage (VAC)  Ue

230

230

    Rated ultimate short-circuit
    breaking ability      
(kA) Icu

    230V

1.5

2.5

    Operating short-circuit breaking ability Ics (%Icu)

50

50

    Protective function

    Overload

    Short-circuit

If the user needs short-circuit protection,  please specify when ordering.

    Short-circuit trip range

(8-16)In

(8-16)In

    Over-current tripping device    

Thermal-magnetic

Thermal-magnetic

    Comply standards

IEC60947-2

IEC60947-2

    Operational performance(times)

    Mechanical life85008500
    Electrical life15001500
Outline dimensions(mm)
图片3.png

    L

7070
    W3232
    H14242
    H24545
    H5757
    Connection    Screw
    Lug
    Mounting(standard)Screw fixedScrew fixed


OUTLINE AND MOUNTING DIMENSIONS


image.png

在线留言

还有问题吗?取得联系。我们很乐意听取您的意见。