RGM1-1250

RGM1-1250 moulded case circuit breaker (hereafter simply referred to as breakers), the rated insulation voltage of the breakers is 800V. In the circuit of AC50Hz/60Hz, rated working voltage 690V or below ,rated current from 800A to 1250A, the breakers take the role of infrequent turn-on or turn-off .The breakers have overload and short-circuit protection devices ,so as to protect the circuit and the power equipment against damage.
Service hotline+86-137-7773-8060 +86-577-89051920
Ask Ouote Now

GENERAL

RGM1-1250 moulded case circuit breaker (hereafter simply referred to as breakers), the rated insulation voltage of the breakers is 800V. In the circuit of AC50Hz/60Hz, rated working voltage 690V or below ,rated current from 800A to 1250A, the breakers take the role of infrequent turn-on or turn-off .The breakers have overload and short-circuit protection devices ,so as to protect the circuit and the power equipment against damage.

The breakers could be installed vertically or horizontally.

The breakers have isolating function and its corresponding symbol is shown as .

The breakers comply with the demands of the following standards:

EN/IEC60947-1 Low-voltage switchgear and controlgear——Part1:General rules.

EN/IEC60947-1 Low-voltage switchgear and controlgear——Part 2:Circuit-breaker.

NORMAL SERVICE AND MOUNTING CONDTIONS

The ambient air temperature does not exceed +40℃ and its average over a period of 24h does not exceed +35℃,the lower limit of the ambient air temperature is -5℃.

The altitude of the site of installation does not exceed 2000m.

The relative humidity of the air does not exceed 50% at a maximum temperature of +40℃ , higher relative humidities may be permitted at lower temperature,e.g.90% at +20℃. Special measures may be necessary in cases of occasional condensation due to variations in temperature.

Pollution degree 3.

Installing category: III for the main circuit , and II for other auxiliary and control circuits.

Be suitable in electromagnetic environment A.

There must be not any explosive medium, and there must be not any gas which would corrode metal or any conducting dust which would destory the insulation

The place would not be invaded by rain and snow. 


MAIN TECHNICAL PERFORMANCE INDEX

   Frame

1250

   Type

RGM1-1250

   Pole number

3

4

   Rated current(A)                    In

800、1000、1250

   Rated insulation voltage(VAC)       Ui

800

800

   Rated impulse withstand vol(V)   Uimp

8000

8000

   Rated operational voltage (VAC)     Ue

400/690

400/690

   Breaking ability code

L

L

   Rated ultimate   short-circuit 

   breaking ability         (kA) Icu

400V

80

80

690V

25

25

   Operating short-circuit breaking ability        Ics (%Icu)  5050
   Arc-over distance(mm)≯100≯100
   CategoryAA
   Over-current tripping device           Thermal-magnetic                     Thermal-magnetic            
   Comply standards IEC60947-2 IEC60947-2
   Operational performance (times)    Mechanical life2500
2500
Electrical life500
500
   Outline dimensions(mm)图片1.pngL
330330
W210
280
H137
137
   Shunt release

   Under-voltage release

   Auxiliary contact

   Alarm contact

   Turning handle mechanism
   Power-driven mechanism


OUTLINE AND MOUNTING DIMENSIONS

Wiring in front of the board

image.png


Type
Pole

LL1L2L3W1W2W3HH1H2H3ABΦd
RGM1-1250L3330
3471001002107078137191
5842702939
4280


CONTACT FORM