RGM1-225L

RGM1-225 moulded case circuit breaker (hereafter simply referred to as breakers), the rated insulation voltage of the breakers is 800V. In the circuit of AC50Hz/60Hz, rated working voltage 690V or below ,rated current from 100A to 250A, the breakers take the role of infrequent turn-on or turn-off .The breakers have overload and short-circuit protection devices ,so as to protect the circuit and the power equipment against damage.
Service hotline+86-137-7773-8060 +86-577-89051920
Ask Ouote Now

GENERAL

RGM1-225 moulded case circuit breaker (hereafter simply referred to as breakers), the rated insulation voltage of the breakers is 800V. In the circuit of AC50Hz/60Hz, rated working voltage 690V or below ,rated current from 100A to 250A, the breakers take the role of infrequent turn-on or turn-off .The breakers have overload and short-circuit protection devices ,so as to protect the circuit and the power equipment against damage.

The breakers according to the rated maximal value to short-circuit breaking ability(Icu),would be classified type L/M/H.

The breakers could be installed vertically or horizontally.

The breakers have isolating function and its corresponding symbol is shown as .

The breakers comply with the demands of the following standards:

EN/IEC60947-1 Low-voltage switchgear and controlgear——Part1:General rules.

EN/IEC60947-1 Low-voltage switchgear and controlgear——Part 2:Circuit-breaker.

NORMAL SERVICE AND MOUNTING CONDTIONS

The ambient air temperature does not exceed +40℃ and its average over a period of 24h does not exceed +35℃,the lower limit of the ambient air temperature is -5℃.

The altitude of the site of installation does not exceed 2000m.

The relative humidity of the air does not exceed 50% at a maximum temperature of +40℃ , higher relative humidities may be permitted at lower temperature,e.g.90% at +20℃. Special measures may be necessary in cases of occasional condensation due to variations in temperature.

Pollution degree 3.

Installing category: III for the main circuit , and II for other auxiliary and control circuits.

Be suitable in electromagnetic environment A.

There must be not any explosive medium, and there must be not any gas which would corrode metal or any conducting dust which would destory the insulation

The place would not be invaded by rain and snow. 


MAIN TECHNICAL PERFORMANCE INDEX

   Frame

225

   Type

RGM1-225

   Pole number

2

3

4

3

4

3

   Rated current(A)                    In

100、125、160、180、200、225、250

   Rated insulation voltage(VAC)       Ui

800

800

800

   Rated impulse withstand vol(V)   Uimp

8000

8000

8000

   Rated operational voltage (VAC)     Ue

400

400/690

400/690

400/690

   Breaking ability code

L

M

H

   Rated ultimate   short-circuit 

   breaking ability         (kA) Icu

400V

25

35

50

690V

/

10

20

   Operating short-circuit breaking ability        Ics (%Icu)  505050
   Arc-over distance(mm)≯50≯50≯50
   CategoryAA
A
   Over-current tripping deviceThermal-magneticThermal-magneticThermal-magnetic
   Comply standards IEC60947-2 IEC60947-2 IEC60947-2
   Operational performance (times)Mechanical life7000
70007000
Electrical life1000
1000
1000
   Outline dimensions(mm)图片1.pngL
165165
165
W75
107142107
142142
H86
103103
   Shunt release

   Under-voltage release

   Auxiliary contact

   Alarm contact

   Turning handle mechanism
   Power-driven mechanism


OUTLINE AND MOUNTING DIMENSIONS

Wiring in front of the board

image.png

TypePoleOutline dimensions(mm)Mounting dimensions(mm)
LL1L2L3W1W2W3HH1H2H3ABΦd
 RGM1-225L   2165144605075352286110242401294.5
310730
4142
 RGM1-225M   3107103127
4142
  RGM1-225H    3
107


Wiring on back of the board

image.png

TypeOutline dimensions(mm)Mounting dimensions(mm)
H1H2L1L2W1W2Φd1Φd2
   RGM1-225  70110144126353524
4.5


Insertion type wiring on back of the board
image.png


TypePoleOutline dimensions(mm)Mounting dimensions(mm)
L1L2H1H2H3MjL3L4WABΦd
   RGM1-225    318614571.55017.58885111070546.5
4145105



CONTACT FORM

Please fill out the below and we will get back to you as soon as possible.
+86-137-7773-8060
Quote Now
rigan@ruiguangelec.com