RGM8-250S

​RGM8-250 moulded case circuit breaker (hereafter simply referred to as breakers), the rated insulation voltage of the breakers is 800V. In the circuit of AC50Hz/60Hz, rated working voltage 690V or below ,rated current from 125A to 250A, the breakers take the role of infrequent turn-on or turn-off .The breakers have overload and short-circuit protection devices ,so as to protect the circuit and the power equipment against damage.
Service hotline+86-137-7773-8060 +86-577-89051920
Ask Ouote Now

GENERAL

RGM8-250 moulded case circuit breaker (hereafter simply referred to as breakers), the rated insulation voltage of the breakers is 800V. In the circuit of AC50Hz/60Hz, rated working voltage 690V or below ,rated current from 125A to 250A, the breakers take the role of infrequent turn-on or turn-off .The breakers have overload and short-circuit protection devices ,so as to protect the circuit and the power equipment against damage.

The breakers could be installed vertically or horizontally.

The breakers have isolating function and its corresponding symbol is shown as .

The breakers comply with the demands of the following standards:

EN/IEC60947-1 Low-voltage switchgear and controlgear——Part1:General rules.

EN/IEC60947-1 Low-voltage switchgear and controlgear——Part 2:Circuit-breaker.

NORMAL SERVICE AND MOUNTING CONDTIONS

The ambient air temperature does not exceed +40℃ and its average over a period of 24h does not exceed +35℃,the lower limit of the ambient air temperature is -5℃.

The altitude of the site of installation does not exceed 2000m.

The relative humidity of the air does not exceed 50% at a maximum temperature of +40℃ , higher relative humidities may be permitted at lower temperature,e.g.90% at +20℃. Special measures may be necessary in cases of occasional condensation due to variations in temperature.

Pollution degree 3.

Installing category: III for the main circuit , and II for other auxiliary and control circuits.

Be suitable in electromagnetic environment A.

There must be not any explosive medium, and there must be not any gas which would corrode metal or any conducting dust which would destory the insulation

The place would not be invaded by rain and snow. 


MAIN TECHNICAL PERFORMANCE INDEX

   Frame

250

   Type

RGM8-250

   Pole number

3

4

   Type of trip unit                             Thermal-magnetic fixed                
               Thermal unfixed-magnetic fixed    
   Rated current   In (A)              Thermal-magnetic fixed                            125、160、180、200、225、250               
              Thermal unfixed-magnetic fixed                 125、160、180、200、225、250    

   Thermal release setting current Ir(×In)

0.8-0.9-1.0

   Rated insulation voltage(VAC)       Ui

800

800

   Rated impulse withstand vol(V)   Uimp

8000

8000

   Rated operational voltage (VAC)     Ue

400

400

   Breaking ability code

S

S

   Rated ultimate   short-circuit 

   breaking ability         (kA) Icu

400V

35

25

690V

-

-

   Operating short-circuit breaking ability        Ics (%Icu)  5050
   Arc-over distance(mm)≯50≯50
   CategoryAA
   Over-current tripping deviceThermal-magnetic Thermal-magnetic   
   Comply standards IEC60947-2 IEC60947-2
   Operational performance (times)    Mechanical life7000
7000
Electrical life1000
1000
   Outline dimensions(mm)图片1.pngL
165165
W          105          
140
H60
60
   Shunt release

   Under-voltage release

   Auxiliary contact

   Alarm contact

   Turning handle mechanism
   Power-driven mechanism


OUTLINE AND MOUNTING DIMENSIONS

Outline dimensions

image.png

TypePoleOutline dimensions(mm)Mounting dimensions(mm)

LL1L2L3L4WW1W2W3HH1H2H3H4H5H6W4L5Φa
 RGM8-250  31651441025080105
3522101
606670865682242589
4140136


Mounting dimensions

image.png

  TypePoleABCΦD
  RGM8-250312635/5
425






CONTACT FORM