RGE54F

RGE50F earth leakage circuit breaker (hereafter simply referred to as breakers), the rated insulation voltage of the breakers is 690V. In the circuit of AC50Hz/60Hz, rated working voltage 600V or below ,rated current from 15A to 50A, the breakers has function of protecting human body from electric shock and equipment from electrical leakage, and it can prevent fire caused by insulation problem of equipment. The breakers also has overload protection devices ,so as to protect the circuit and the power equipment against damage.
Service hotline+86-137-7773-8060 +86-577-89051920
Ask Ouote Now

GENERAL

RGE50F earth leakage circuit breaker (hereafter simply referred to as breakers), the rated insulation voltage of the breakers is 690V. In the circuit of AC50Hz/60Hz, rated working voltage 600V or below ,rated current from 15A to 50A, the breakers has function of protecting human body from electric shock and equipment from electrical leakage, and it can prevent fire caused by insulation problem of equipment. The breakers also has overload protection devices ,so as to protect the circuit and the power equipment against damage.

The breakers could be installed vertically or horizontally.

The breakers have isolating function and its corresponding symbol is shown as .

The breakers comply with the demands of the following standards:

EN/IEC60947-1 Low-voltage switchgear and controlgear——Part1:General rules.

EN/IEC60947-2 Low-voltage switchgear and controlgear——Part 2:Circuit-breaker.

NORMAL SERVICE AND MOUNTING CONDTIONS

The ambient air temperature does not exceed +40℃ and its average over a period of 24h does not exceed +35℃,the lower limit of the ambient air temperature is -5℃.

The altitude of the site of installation does not exceed 2000m.

The relative humidity of the air does not exceed 50% at a maximum temperature of +40℃ , higher relative humidities may be permitted at lower temperature,e.g.90% at +20℃. Special measures may be necessary in cases of occasional condensation due to variations in temperature.

Pollution degree 3.

Installing category: III for the main circuit , and II for other auxiliary and control circuits.

Be suitable in electromagnetic environment A.

There must be not any explosive medium, and there must be not any gas which would corrode metal or any conducting dust which would destory the insulation

The place would not be invaded by rain and snow. 


MAIN TECHNICAL PERFORMANCE INDEX

    Frame

50

    Type

RGE52F

RGE53F

RGE54F

    Pole&Element

2P2E

3P3E

4P4E

    Wiring system

1Φ2W

3Φ3W

3Φ4W

    Rated current(A)                 In

15、20、30、40、50

15、20、30、40、50

15、20、30、40、50

    Rated insulation voltage(VAC)    Ui

690

690

690

    Rated impulse withstand vol(V)   Uimp

6000

6000

6000

    Rated operational voltage (VAC)  Ue

230

415

415

    Rated ultimate short-circuit
    breaking ability      (kA) Icu

    230V

5

/

/

    415V

/

5

5

    Operating short-circuit breaking ability Ics (%Icu)

50

50

50

    Category

A

A

A

    Rated residual  operating current(mA) I△n

image.png15,30

image.png15,30

image.png15,30

    Residual current off-time at I△n (sec)

≯0.1

≯0.1

≯0.1

    Protective function

    Electric leakage

    Overload

    Short-circuit

    Over-current tripping device

Hydraulic-magnetic

Hydraulic-magnetic

Hydraulic-magnetic

    Short-circuit trip range

(5-10)In

(5-10)In

(5-10)In

    Comply standards

IEC60947-2

IEC60947-2

IEC60947-2

    Operational performance(times)

    Mechanical life850085008500
    Electrical life150015001500
Outline dimensions(mm)图片1.png

    L

969696
    W5075100
    H606060
    Connection    Screw
    Lug
    Mounting(standard)Screw fixed/DIN RailScrew fixed/DIN RailScrew fixed/DIN Rail
    Accessories
 ■ ■ ■


OUTLINE AND MOUNTING DIMENSIONS

image.png
                   RGE52F                                          RGE53F                                                   RGE54F



CONTACT FORM

Please fill out the below and we will get back to you as soon as possible.
+86-137-7773-8060
Quote Now
rigan@ruiguangelec.com