HGM-100 series moulded case circuit breaker (hereafter simply referred to as breakers), the rated insulation voltage of the breakers is 1000V. In the circuit of AC50Hz/60Hz, rated working voltage 690V or below ,rated current from 5A to 100A, the breakers take the role of infrequent turn-on or turn-off .The breakers have overload and short-circuit protection devices ,so as to protect the circuit and the power equipment against damage.

The breakers could be installed vertically or horizontally.

The breakers have isolating function and its corresponding symbol is shown asimage.png .

The breakers comply with the demands of the following standards:

IEC60947-1 and GB14048.1  Low-voltage switchgear and controlgear——Part1:General rules.

IEC60947-2 and GB/T14048.2  Low-voltage switchgear and controlgear——Part 2:Circuit-breaker.


NORMAL SERVICE AND MOUNTING CONDTIONS

The ambient air temperature does not exceed +40℃ and its average over a period of 24h does not exceed +35℃,the lower limit of the ambient air temperature is -5℃.

The altitude of the site of installation does not exceed 2000m.

The relative humidity of the air does not exceed 50% at a maximum temperature of +40℃ , higher relative humidities may be permitted at lower temperature,e.g.90% at +20℃. Special measures may be necessary in cases of occasional condensation due to variations in temperature.

Pollution degree 3.

Installing category: III for the main circuit , and II for other auxiliary and control circuits.

Be suitable in electromagnetic environment A.

There must be not any explosive medium, and there must be not any gas which would corrode metal or any conducting dust which would destory the insulation

The place would not be invaded by rain and snow. 


MAIN TECHNICAL PERFORMANCE INDEX

    Frame

100

    Type

HGM-100

    Pole number

3

    Rated current(A)                         In

5、6、10、15、16、20、30、32、40、50、60、75、80、100

    Rated insulation voltage(VAC)    Ui

AC1000

    Rated impulse withstand vol(V)   Uimp

8000

    Rated operational voltage (VAC)  Ue

AC690

    Rated ultimate short-circuit breaking ability      (kA) Icu

   660/690V2.5
   480/500V

7.5

   440/460V

16

   380/415V

16

    Operating short-circuit breaking ability  (kA) Ics

100

    Category

A

    Over-current tripping device

Thermal-magnetic Fixed

Thermal-magnetic Adjustable

(0.8、0.9、1.0)×In

    Operating current of short-circuit protection(A)

16-32A 400A 40-100A 10×10In

    Comply standards

IEC60947-2

    Operational performance (times)

    Mechanical life

25000
    Electrical life10000
    Outlion dimensions(mm)图片2.pngL130
W75
H68


NORMAL SERVICE AND MOUNTING CONDTIONS

image.png