HGM100 3P
GENERAL
HGM-100 series moulded case circuit breaker (hereafter simply referred to as breakers), the rated insulation voltage of the breakers is 1000V. In the circuit of AC50Hz/60Hz, rated working voltage 690V or below ,rated current from 5A to 100A, the breakers take the role of infrequent turn-on or turn-off .The breakers have overload and short-circuit protection devices ,so as to protect the circuit and the power equipment against damage.
The breakers could be installed vertically or horizontally.
The breakers have isolating function and its corresponding symbol is shown as .
The breakers comply with the demands of the following standards:
IEC60947-1 and GB14048.1 Low-voltage switchgear and controlgear——Part1:General rules.
IEC60947-2 and GB/T14048.2 Low-voltage switchgear and controlgear——Part 2:Circuit-breaker.
NORMAL SERVICE AND MOUNTING CONDTIONS
The ambient air temperature does not exceed +40℃ and its average over a period of 24h does not exceed +35℃,the lower limit of the ambient air temperature is -5℃.
The altitude of the site of installation does not exceed 2000m.
The relative humidity of the air does not exceed 50% at a maximum temperature of +40℃ , higher relative humidities may be permitted at lower temperature,e.g.90% at +20℃. Special measures may be necessary in cases of occasional condensation due to variations in temperature.
Pollution degree 3.
Installing category: III for the main circuit , and II for other auxiliary and control circuits.
Be suitable in electromagnetic environment A.
There must be not any explosive medium, and there must be not any gas which would corrode metal or any conducting dust which would destory the insulation
The place would not be invaded by rain and snow.
MAIN TECHNICAL PERFORMANCE INDEX
Frame | 100 | ||
Type | HGM-100 | ||
Pole number | 3 | ||
Rated current(A) In | 5、6、10、15、16、20、30、32、40、50、60、75、80、100 | ||
Rated insulation voltage(VAC) Ui | AC1000 | ||
Rated impulse withstand vol(V) Uimp | 8000 | ||
Rated operational voltage (VAC) Ue | AC690 | ||
Rated ultimate short-circuit breaking ability (kA) Icu | 660/690V | 2.5 | |
480/500V | 7.5 | ||
440/460V | 16 | ||
380/415V | 16 | ||
Operating short-circuit breaking ability (kA) Ics | 100 | ||
Category | A | ||
Over-current tripping device | Thermal-magnetic Fixed Thermal-magnetic Adjustable (0.8、0.9、1.0)×In | ||
Operating current of short-circuit protection(A) | 16-32A 400A 40-100A 10×10In | ||
Comply standards | IEC60947-2 | ||
Operational performance (times) | Mechanical life | 25000 | |
Electrical life | 10000 | ||
Outlion dimensions(mm) | L | 130 | |
W | 75 | ||
H | 68 |