RGM3HU-320

Service hotline+86-137-7773-8060 +86-577-89051920
Ask Ouote Now

GENERAL

RGM3HU series moulded case circuit breaker (hereafter simply referred to as breakers), the maximum rated voltage of the breakers is 1140V,and the maximum current is 800A.In the voltage of AC800V,the maximum breaking capacity is 50kA,which can ensure reliable short-circuit protection of the system. 

The breakers could be installed vertically or horizontally.

The breakers comply with the demands of the following standards:

IEC60947-1 and GB14048.1  Low-voltage switchgear and controlgear——Part1:General rules.

IEC60947-2 and GB/T14048.2  Low-voltage switchgear and controlgear——Part 2:Circuit-breaker.


NORMAL SERVICE AND MOUNTING CONDTIONS

The ambient air temperature does not exceed +40℃ and its average over a period of 24h does not exceed +35℃,the lower limit of the ambient air temperature is -5℃.

The altitude of the site of installation does not exceed 5500m.

It is resistant to damp air(three-proof type).

It is resistant to the influence of salt fog and oil fog(three-proof type).

It is resistant to the influence of mold(three-proof type).

In a medium without explosion risk, and the medium is not enough to corrode the metal and destroy the insulation of the gas and conductive dust.

Note: The three-prevention products should be specially customized, please indicate TH.


MAIN TECHNICAL PERFORMANCE INDEX

   Frame320
   TypeRGM3HU-320
   Pole number3
   Rated current(A)                         In

63,80,100,125,140,160,180,200,225,250,280,315,320

   Rated insulation voltage(V)        Ui

AC1150
   Rated impulse withstand vol(V)  Uimp8
   Rated operational voltage (V)     Ue415500/6908001000/1140

   Rated ultimate short-circuit  breaking ability      (kA) Icu

1206536.515
   Operating short-circuit breaking ability  (kA) Ics85
5036.515
   Wiring mode

Up incoming and down outcoming

   Arc-over distance(mm)≯50(Zero arc with arcing cover)
   Allowable ambient temperature-40~+70℃

   Levels of protection

IP20
   Transient Action value10ln
   Comply standards

IEC60947-2

  Operational performance (times)

Mechanical life

20000
Electrical life3000
300030002000
   Outline dimensions(mm)image.pngL
180
W107
H126
   Shunt release
   Auxiliary contact
   Alarm contact
  Turning handle mechanism
   Power-driven mechanism